Skip to main content

Electrolyser

Telemetry

FieldDescription
timestampMessage publishing timestamp
statusElectrolyser states
alertsList of electrolyser errors and warnings
LSHH102A_inIndicates whether electrolyte level is higher than very high level
LSH102B_inIndicates whether electrolyte level is higher than high level
LSM102C_inIndicates whether electrolyte level is higher than medium level
LSL102D_inIndicates whether electrolyte level is higher than low level
h2_flowH2 Production in Normal Litre/hour
h2_totalTotal H2 Produced in Normal Litre
PT101A_in_barH2 Stack Pressure in Bar
PSU_in_vH2 Stack Voltage in Volt
HASS_in_aH2 Stack Amperage in Ampere
PT101C_in_barH2 Outlet Pressure in Bar
PT105_in_barWater Inlet Pressure in Bar
TT102A_in_cElectrolyte Tank Temperature in Celsius
TT106_in_cDownstream Temperature in Celsius

Commands

Command NameDescriptionArguments
startStart electrolyser
stopStop electrolyser
resetReset electrolyser
set_production_rateSet electrolyser production rate (in percents)value (float)
set_waterfillForce electrolyser to perform water refill operationvalue (boolean) (should be set to true)

Electrolyser States

State
maintenance
expert
halt
error
fatal
idle
steady
standby
curve
blowdown